Hazardous material cabinet for the active storage of lithium-ion batteries, offers fire protection from inside and has a sophisticated, 3 level fire warning/ suppression / system. All five shelves are equipped with a socket board, attached to the back of the cabinet, housing 8 protected sockets. Delivered, ready to be connected to the mains power supply with technical air extraction ( to avoid heat in the inner room) Supplied complete with tested, liquid-tight spill pallet (powder coated sheet steel) for containment of any leakage from burning batteries.
- Permanently self closing doors and quality oil-dampened door closers
- Doors can be locked with profile cylinder (closing system compatible) and lock indicator (red/green)
- Adjustable feet for use on uneven floor surfaces
- Robust construction with scratch-proof paint
- Integral base, accessible underneath, making it easy to change location (base can be closed off with optional panel)
- Socket board total output - standard 1-phase, 230 V, 13 A fuse, max. permitted total output = 2.99 kW. Available as an option: 3-phase, 400 V, 3 x 13A fuse, max. permitted total output = 8.97kW
Hazardous materials cabinets for the passive or active storage of lithium-ion batteries in accordance with DIN EN 14470-1 and DIN EN 1363-1 with a fire resistance of 90 minutes (Type 90) - fire protection from outside in. In addition cabinets also have 90 minutes fire resistance from inside to out. Cabinets are a storage compartment in accordance with TRGS 510 - So the requirements of VdS 3103:2016-05 are met.
Body colour: Anthracite Grey (RAL 7016)
Doors: 2 winged doors Gentian Blue (RAL 5010)
Technical Data
- External Dimensions: 1193W x 615D x 2224H** (mm)
- Internal Dimensions: 1050W x 522D x 1647H (mm)
- Weight excluding interior equipment: 424 kg
- Maximum load: 600 kg
- Load capacity shelf: 33 kg
- Sump capacity: 33 Litres
Specifications
- Shelves*: 5
- Socket boards: 5 with 8 sockets
- Total number of charging points: 40
*Position of shelves and socket boards are fixed and cannot be changed